- 首頁
- 巡檢紀錄
- 設備巡檢結果
- 詳細資訊
- 表單顯示
TRANE 離心式冰水主機I3-CHM-RF-01
設備巡檢紀錄 - TRANE 離心式冰水主機檢查表
|
檢查項目
|
參考值
|
單位
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
13
|
14
|
15
|
16
|
17
|
18
|
19
|
20
|
21
|
22
|
23
|
24
|
25
|
26
|
27
|
28
|
29
|
30
|
31
|
|
電流 L1 |
|
A |
NA
|
NA
|
NA
|
NA
|
NA
|
115.5 |
123.5 |
122 |
NA
|
NA
|
116 |
133.1 |
123.7 |
114.7 |
NA
|
NA
|
123.3 |
120.9 |
121.5 |
108.6 |
|
|
|
|
|
|
|
|
|
|
|
|
電流 L2 |
|
A |
NA
|
NA
|
NA
|
NA
|
NA
|
119.5 |
129.2 |
128 |
NA
|
NA
|
125 |
139 |
132.9 |
122.4 |
NA
|
NA
|
132.5 |
124.5 |
123.5 |
111.8 |
|
|
|
|
|
|
|
|
|
|
|
|
電流 L3 |
|
A |
NA
|
NA
|
NA
|
NA
|
NA
|
126.9 |
135.8 |
134 |
NA
|
NA
|
130 |
140 |
143.9 |
132.2 |
NA
|
NA
|
143.2 |
132.5 |
130.5 |
121.1 |
|
|
|
|
|
|
|
|
|
|
|
|
實際電流值 |
|
% |
348.7 |
350 |
352.7 |
349.5 |
350 |
40 |
45 |
44.8 |
NA
|
346 |
45 |
45 |
45 |
45 |
340 |
NA
|
45 |
45 |
45 |
40 |
|
|
|
|
|
|
|
|
|
|
|
|
吐出油壓 |
40~103 |
Kpa |
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
油槽壓力 |
≧-83 |
Kpa |
646 |
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
油槽壓差 |
82~170 |
Kpa |
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
油槽溫度 |
40~66 |
℃ |
54.6 |
54.6 |
55.3 |
55.2 |
55.2 |
51.2 |
51.8 |
50.4 |
NA
|
53.2 |
51.5 |
51.1 |
NA
|
NA
|
52.4 |
53.2 |
51.1 |
51.5 |
51.5 |
51.5 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器冷媒壓力 |
-80~-30 |
Kpa |
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器冷媒壓力 |
0~83 |
Kpa |
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器趨近溫度 |
|
℃ |
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器趨近溫度 |
|
℃ |
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器進水溫度 |
|
℃ |
9.6 |
9.6 |
9.5 |
9.6 |
9.8 |
9.8 |
9.7 |
9.7 |
NA
|
9.7 |
9.6 |
9.8 |
9.7 |
9.7 |
9.7 |
9.7 |
9.7 |
9.7 |
9.7 |
9.4 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器出水溫度 |
6~12 |
℃ |
6.9 |
6.9 |
6.8 |
6.9 |
7.1 |
7.2 |
7.0 |
7.1 |
NA
|
7 |
6.9 |
7 |
7 |
7.1 |
7 |
7.1 |
6.9 |
7 |
7 |
6.8 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器進水溫度 |
≦32 |
℃ |
29 |
29.3 |
29.4 |
29.3 |
29 |
28 |
28 |
28 |
NA
|
28.7 |
27.7 |
29.7 |
28.5 |
27.7 |
28.3 |
28.7 |
28.3 |
28.4 |
28.6 |
27.6 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器出水溫度 |
≦37 |
℃ |
31.4 |
31.7 |
31.8 |
31.5 |
31.4 |
30.3 |
30.3 |
30 |
NA
|
31.1 |
30.1 |
32.2 |
31.5 |
30 |
30.5 |
31.2 |
30.8 |
30.7 |
30.5 |
29.7 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器進出水壓差 |
≧0.3 |
kg/cm2 |
0.4 |
0.4 |
0.6 |
0.5 |
0.5 |
0.5 |
1 |
0.5 |
NA
|
0.6 |
0.5 |
1 |
1 |
1 |
0.6 |
0.6 |
1 |
1 |
0.8 |
1 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器進出水壓差 |
≧0.5 |
kg/cm2 |
0.5 |
0.5 |
0.8 |
0.8 |
0.8 |
0.5 |
1 |
0.8 |
NA
|
0.6 |
1 |
1 |
1 |
1 |
0.8 |
0.8 |
1 |
1 |
0.8 |
1 |
|
|
|
|
|
|
|
|
|
|
|
| 備註 |
1.(V):正常/(X):異常;有操作參數則需填入檢查數據。
2.若該設備無此項檢查項目時,請填寫NA。
3.此表單由廠房設施部存查,保存期限三年。
|
| 紀錄者 |
張家韋
|
張家韋
|
張家韋
|
張家韋
|
黃立凱
|
黃立凱
|
黃立凱
|
楊植鈞
|
張家韋
|
張家韋
|
黃立凱
|
黃立凱
|
黃立凱
|
黃立凱
|
張家韋
|
張家韋
|
黃立凱
|
黃立凱
|
黃立凱
|
黃立凱
|
|
|
|
|
|
|
|
|
|
|
|