勇日 DB-30LD 吸附式乾燥機HQ-MDM-B2-01
設備巡檢紀錄 - 勇日 DB-30LD 吸附式乾燥機檢查表
|
檢查項目
|
參考值
|
單位
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
13
|
14
|
15
|
16
|
17
|
18
|
19
|
20
|
21
|
22
|
23
|
24
|
25
|
26
|
27
|
28
|
29
|
30
|
31
|
|
出口露點溫度 |
≦-40 |
℃ |
-50.8 |
-50.8 |
-46.7 |
-47.9 |
-50.9 |
-49.8 |
-49.9 |
-47.1 |
-49.9 |
-49.7 |
-50.1 |
-49.6 |
-49 |
-49.8 |
-49.9 |
-50 |
-50.1 |
-47.8 |
-51.1 |
-50 |
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽壓力 |
|
Bar |
7.18 |
7.16 |
7.22 |
7.18 |
7.16 |
7.17 |
7.16 |
7.16 |
7.17 |
7.19 |
7.17 |
7.18 |
7.16 |
7.18 |
7.19 |
7.16 |
7.18 |
7.15 |
7.18 |
7.14 |
|
|
|
|
|
|
|
|
|
|
|
|
再生加熱溫度TT1 |
15~200 |
℃ |
177.9 |
176 |
43 |
46.2 |
51.2 |
63.1 |
171 |
44.1 |
174 |
70.2 |
70.2 |
74.1 |
174 |
173 |
178 |
177 |
178 |
40.1 |
50.2 |
65.2 |
|
|
|
|
|
|
|
|
|
|
|
|
再生端出口溫度TT2 |
|
℃ |
40 |
43 |
42.1 |
46.1 |
52.1 |
62 |
43.1 |
43 |
78 |
72 |
73 |
78.9 |
44.1 |
39.1 |
43.1 |
42.1 |
42.1 |
40 |
53.2 |
64.1 |
|
|
|
|
|
|
|
|
|
|
|
|
再生冷卻端入口溫度TT3 |
|
℃ |
37.1 |
39 |
36.1 |
54.1 |
71.1 |
119 |
57.1 |
37 |
59.1 |
153 |
153.1 |
138 |
59.1 |
42.9 |
57 |
55.1 |
54 |
34 |
67.1 |
135.9 |
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽ADS1 |
|
|
V
|
V
|
V
|
V
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
V
|
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽ADS2 |
|
|
NA
|
NA
|
NA
|
NA
|
V
|
V
|
V
|
NA
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
再生桶槽ADS1 |
|
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
V
|
NA
|
NA
|
NA
|
V
|
V
|
V
|
V
|
V
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
再生桶槽ADS2 |
|
|
V
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水入口溫度(管路) |
|
℃ |
38 |
37 |
34 |
31 |
32 |
33 |
NA
|
NA
|
41 |
34 |
34 |
35 |
NA
|
NA
|
40 |
39 |
39 |
37 |
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出口溫度(管路) |
|
℃ |
32 |
33 |
30 |
30 |
30 |
32 |
NA
|
NA
|
36 |
33 |
33 |
34 |
NA
|
NA
|
34 |
34 |
34 |
33 |
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水入口壓力(管路) |
|
kg/cm2 |
7.4 |
7.2 |
7.8 |
7.7 |
7.6 |
7.7 |
8 |
8 |
7.7 |
7.7 |
7.6 |
7.8 |
8 |
8 |
7.8 |
7.9 |
7.7 |
8 |
8 |
8 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出口壓力(管路) |
|
kg/cm2 |
6 |
6 |
5.8 |
5.8 |
5.8 |
5.8 |
6 |
6 |
5.8 |
5.8 |
5.8 |
5.8 |
6 |
6 |
5.8 |
5.8 |
5.8 |
5.8 |
6 |
6 |
|
|
|
|
|
|
|
|
|
|
|
|
前置過濾器壓差 |
≦0.4 |
Bar |
0 |
0 |
0.1 |
0.1 |
0.1 |
0.1 |
0.05 |
0.05 |
0.1 |
0.1 |
0.1 |
0.1 |
0.04 |
0.03 |
0.1 |
0.1 |
0.1 |
0.1 |
0.04 |
0.05 |
|
|
|
|
|
|
|
|
|
|
|
|
後置過濾器壓差 |
≦0.4 |
Bar |
0.1 |
0 |
0.1 |
0.1 |
0.1 |
0.1 |
0.06 |
0.07 |
0.1 |
0.1 |
0.1 |
0.1 |
0.08 |
0.07 |
0.1 |
0.1 |
0.1 |
0.1 |
0.05 |
0.08 |
|
|
|
|
|
|
|
|
|
|
|
|
却水器檢查 |
|
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
|
|
|
|
|
|
|
|
|
|
|
| 備註 |
1.(V):正常/(X):異常;有操作參數則需填入檢查數據。
2.若該設備無此項檢查項目時,請填寫NA。
3.此表單由廠房設施部存查,保存期限三年。
|
| 紀錄者 |
洪耀懋
|
洪耀懋
|
王清雲
|
王清雲
|
王清雲
|
王清雲
|
張家韋
|
張家韋
|
王清雲
|
王清雲
|
王清雲
|
王清雲
|
張家韋
|
張家韋
|
王清雲
|
王清雲
|
王清雲
|
王清雲
|
張家韋
|
張家韋
|
|
|
|
|
|
|
|
|
|
|
|