勇日 DB-30LD 吸附式乾燥機HQ-MDM-B2-02
設備巡檢紀錄 - 勇日 DB-30LD 吸附式乾燥機檢查表
|
檢查項目
|
參考值
|
單位
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
13
|
14
|
15
|
16
|
17
|
18
|
19
|
20
|
21
|
22
|
23
|
24
|
25
|
26
|
27
|
28
|
29
|
30
|
31
|
|
出口露點溫度 |
≦-40 |
℃ |
-44.3 |
-49.8 |
-79.3 |
-51.4 |
-80.8 |
-49.9 |
-44.2 |
-46.1 |
-73.5 |
-51.2 |
-44.6 |
-49.4 |
-44.6 |
-55.4 |
-83.3 |
-50.2 |
-84.9 |
-50 |
-44.8 |
-56.8 |
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽壓力 |
|
Bar |
7.18 |
7.14 |
7.18 |
7.19 |
7.15 |
7.17 |
7.17 |
7.16 |
7.20 |
7.16 |
7.15 |
7.16 |
7.23 |
7.18 |
7.17 |
7.18 |
7.18 |
7.20 |
7.18 |
7.16 |
|
|
|
|
|
|
|
|
|
|
|
|
再生加熱溫度TT1 |
15~200 |
℃ |
30.1 |
37.1 |
30.9 |
37.2 |
31 |
38.2 |
31 |
34.2 |
31 |
39 |
31 |
38.2 |
31 |
39.1 |
31 |
38.1 |
179.2 |
37.2 |
32.1 |
40 |
|
|
|
|
|
|
|
|
|
|
|
|
再生端出口溫度TT2 |
|
℃ |
30.9 |
34 |
31.9 |
34 |
30.9 |
34 |
31.9 |
32.9 |
30.9 |
35.1 |
27 |
35.9 |
30.9 |
36 |
32 |
36 |
36 |
33 |
30.9 |
37.9 |
|
|
|
|
|
|
|
|
|
|
|
|
再生冷卻端入口溫度TT3 |
|
℃ |
27 |
29.1 |
27 |
29.1 |
27 |
29.1 |
27 |
28 |
27 |
30.1 |
31 |
29.1 |
27 |
32.1 |
27 |
29 |
35.1 |
29.1 |
27 |
35.2 |
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽ADS1 |
|
|
V
|
V
|
V
|
V
|
NA
|
NA
|
NA
|
NA
|
V
|
V
|
V
|
V
|
NA
|
V
|
V
|
V
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽ADS2 |
|
|
NA
|
NA
|
NA
|
NA
|
V
|
V
|
V
|
V
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
NA
|
V
|
V
|
V
|
V
|
|
|
|
|
|
|
|
|
|
|
|
|
再生桶槽ADS1 |
|
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
再生桶槽ADS2 |
|
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水入口溫度(管路) |
|
℃ |
12 |
12 |
12 |
10 |
10 |
10 |
NA
|
10 |
12 |
13 |
11 |
11 |
10 |
10 |
11 |
12 |
13 |
10 |
10 |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出口溫度(管路) |
|
℃ |
15 |
15 |
14 |
13 |
14 |
14 |
12 |
15 |
14 |
15 |
14 |
14 |
14 |
14 |
14 |
14 |
15 |
13 |
14 |
14 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水入口壓力(管路) |
|
kg/cm2 |
7.2 |
7.2 |
7.3 |
7.2 |
7.3 |
7.4 |
7 |
7 |
7.3 |
7.7 |
7.2 |
6.9 |
7.5 |
7 |
7.3 |
7.2 |
7.3 |
7 |
7 |
7.2 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出口壓力(管路) |
|
kg/cm2 |
6 |
6 |
5.9 |
5.9 |
5.9 |
5.9 |
6 |
6 |
6.9 |
5.9 |
6.8 |
5.9 |
6 |
6 |
5.8 |
5.8 |
6 |
5.9 |
6 |
6 |
|
|
|
|
|
|
|
|
|
|
|
|
前置過濾器壓差 |
≦0.4 |
Bar |
0 |
0 |
0.1 |
0.1 |
0.1 |
0.1 |
0.09 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.09 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
|
|
|
|
|
|
|
|
|
|
|
|
後置過濾器壓差 |
≦0.4 |
Bar |
0.1 |
0 |
0.1 |
0.1 |
0.1 |
0.1 |
0.07 |
0.07 |
0.1 |
0.1 |
0.1 |
0.1 |
0.09 |
0.06 |
0.1 |
0.1 |
0.1 |
0.1 |
0.07 |
0.06 |
|
|
|
|
|
|
|
|
|
|
|
|
却水器檢查 |
|
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
|
|
|
|
|
|
|
|
|
|
|
| 備註 |
1.(V):正常/(X):異常;有操作參數則需填入檢查數據。
2.若該設備無此項檢查項目時,請填寫NA。
3.此表單由廠房設施部存查,保存期限三年。
|
| 紀錄者 |
洪耀懋
|
洪耀懋
|
王清雲
|
王清雲
|
王清雲
|
王清雲
|
張家韋
|
張家韋
|
王清雲
|
王清雲
|
王清雲
|
王清雲
|
張家韋
|
張家韋
|
王清雲
|
王清雲
|
王清雲
|
王清雲
|
張家韋
|
張家韋
|
|
|
|
|
|
|
|
|
|
|
|