檢查項目
|
參考值
|
單位
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
13
|
14
|
15
|
16
|
17
|
18
|
19
|
20
|
21
|
22
|
23
|
24
|
25
|
26
|
27
|
28
|
29
|
30
|
31
|
|
冰水入口溫度 |
|
℃ |
10.4 |
11.4 |
11.4 |
10.8 |
13.2 |
10.3 |
14.3 |
13.0 |
13 |
12.6 |
9.3 |
10.5 |
10.9 |
9.9 |
12.8 |
11.1 |
10.5 |
12.6 |
12.5 |
10.9 |
|
|
|
|
|
|
|
|
|
|
|
|
冰水出口溫度 |
|
℃ |
6.1 |
7.2 |
6.6 |
6.5 |
8.1 |
5.9 |
9.4 |
7.9 |
7.9 |
8 |
4.7 |
6.1 |
5.9 |
5.3 |
7.8 |
6 |
6.2 |
7.9 |
7.4 |
6 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水入水溫度 |
|
℃ |
33.3 |
33.3 |
31.8 |
32 |
29.6 |
32.1 |
29.9 |
28.8 |
30 |
31.7 |
32.4 |
33.4 |
30 |
31.6 |
30.7 |
30.2 |
32.1 |
30.5 |
29.6 |
29.7 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出水溫度 |
|
℃ |
37 |
37.1 |
35.8 |
36 |
33.6 |
35.9 |
34.1 |
33.0 |
34.2 |
35.8 |
36.1 |
37.3 |
33.9 |
35.4 |
34.8 |
34.2 |
36 |
34.6 |
33.7 |
33.6 |
|
|
|
|
|
|
|
|
|
|
|
|
電壓 |
418~462 |
V
|
450 |
449.6 |
451 |
454 |
456 |
453.2 |
450 |
456.3 |
453.9 |
447.8 |
448.1 |
448 |
451.7 |
451.4 |
449.3 |
446.5 |
452.6 |
455.1 |
452.9 |
449 |
|
|
|
|
|
|
|
|
|
|
|
|
電流 |
≦200 |
A |
197 |
198.7 |
199 |
197 |
192.6 |
200 |
197 |
189.7 |
194.8 |
200 |
198.8 |
200 |
192.3 |
197.5 |
198.9 |
194.6 |
190.9 |
195.9 |
192.2 |
191.6 |
|
|
|
|
|
|
|
|
|
|
|
|
負載率 |
≦100 |
% |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
運轉時數 |
|
Hr |
732 |
755 |
780 |
803 |
829 |
853 |
876 |
902 |
924 |
947 |
972 |
992 |
1021 |
1044 |
1068 |
1091 |
1118 |
1140 |
1166 |
1187 |
|
|
|
|
|
|
|
|
|
|
|
|
高壓端冷媒壓力 |
≦170 |
PSI |
150 |
150 |
150 |
150 |
145 |
150 |
140 |
140 |
145 |
150 |
150 |
135 |
130 |
140 |
150 |
140 |
135 |
140 |
140 |
140 |
|
|
|
|
|
|
|
|
|
|
|
|
低壓端冷媒壓力 |
≧25 |
PSI |
40 |
40 |
40 |
40 |
45 |
40 |
40 |
43 |
45 |
45 |
25 |
30 |
30 |
30 |
145 |
45 |
30 |
30 |
30 |
30 |
|
|
|
|
|
|
|
|
|
|
|
|
油壓 |
100~170 |
PSI |
145 |
145 |
145 |
145 |
150 |
140 |
140 |
135 |
130 |
145 |
130 |
130 |
130 |
135 |
145 |
140 |
140 |
135 |
140 |
135 |
|
|
|
|
|
|
|
|
|
|
|
|
冰水進水壓力 |
|
Kg/cm2 |
1.8 |
1.5 |
1.8 |
1.6 |
1.8 |
1.6 |
1.8 |
1.6 |
1.8 |
1.2 |
2 |
1.8 |
2 |
2 |
1.8 |
2 |
1.0 |
1.6 |
1.8 |
2 |
|
|
|
|
|
|
|
|
|
|
|
|
冰水出水壓力 |
|
Kg/cm2 |
1.5 |
1 |
1.8 |
1 |
1.6 |
1.2 |
1.2 |
1.4 |
1 |
1 |
1.8 |
1.6 |
1.8 |
1.8 |
1.4 |
1.8 |
1 |
1 |
1.6 |
1.8 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水進水壓力 |
|
Kg/cm2 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出水壓力 |
|
Kg/cm2 |
0.8 |
0.4 |
0.4 |
0.4 |
0.5 |
0.4 |
0.4 |
0.8 |
0.4 |
0.4 |
0.4 |
0.2 |
0.4 |
0.2 |
0.4 |
0.4 |
0.2 |
0.4 |
0.4 |
0.4 |
|
|
|
|
|
|
|
|
|
|
|
| 備註 |
1.(V):正常/(X):異常;有操作參數則需填入檢查數據。
2.若該設備無此項檢查項目時,請填寫NA。
3.此表單由廠房設施部存查,保存期限三年。
|
| 紀錄者 |
張家韋
|
張家韋
|
張家韋
|
張家韋
|
黃立凱
|
黃立凱
|
黃立凱
|
楊植鈞
|
張家韋
|
張家韋
|
黃立凱
|
黃立凱
|
黃立凱
|
黃立凱
|
張家韋
|
張家韋
|
黃立凱
|
黃立凱
|
黃立凱
|
黃立凱
|
|
|
|
|
|
|
|
|
|
|
|