- 首頁
- 巡檢紀錄
- 設備巡檢結果
- 詳細資訊
- 表單顯示
勇日 DB-30LD 吸附式乾燥機HQ-MDM-B2-04
設備巡檢紀錄 - 勇日 DB-30LD 吸附式乾燥機檢查表
|
檢查項目
|
參考值
|
單位
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
13
|
14
|
15
|
16
|
17
|
18
|
19
|
20
|
21
|
22
|
23
|
24
|
25
|
26
|
27
|
28
|
29
|
30
|
31
|
|
出口露點溫度 |
≦-40 |
℃ |
-47.8 |
-52.6 |
-77.1 |
-46.6 |
NA
|
-77.9 |
-69.1 |
-70.1 |
-79.1 |
-69.9 |
-60.9 |
NA
|
-42.3 |
-81 |
-78.6 |
-40.1 |
-57.5 |
-79.1 |
-80.8 |
-42.4 |
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽壓力 |
|
Bar |
7.26 |
7.21 |
7.23 |
7.22 |
NA
|
7.24 |
7.23 |
7.23 |
7.24 |
7.18 |
7.20 |
NA
|
7.25 |
7.24 |
7.21 |
7.23 |
7.27 |
7.23 |
7.2 |
7.22 |
|
|
|
|
|
|
|
|
|
|
|
|
再生加熱溫度TT1 |
15~200 |
℃ |
35.2 |
36.2 |
167 |
34.2 |
NA
|
162.2 |
47.2 |
130 |
159 |
119.1 |
33.2 |
NA
|
35.2 |
159 |
159 |
34.2 |
35.2 |
159.1 |
159 |
34.2 |
|
|
|
|
|
|
|
|
|
|
|
|
再生端出口溫度TT2 |
|
℃ |
42.1 |
50.2 |
43.2 |
39.2 |
NA
|
40.2 |
68.2 |
27.2 |
41.1 |
30.1 |
40.2 |
NA
|
41.1 |
44.2 |
42.1 |
40.2 |
42.1 |
42.1 |
44.2 |
40.2 |
|
|
|
|
|
|
|
|
|
|
|
|
再生冷卻端入口溫度TT3 |
|
℃ |
41.9 |
55 |
42.9 |
39.1 |
NA
|
47.9 |
166.8 |
39.1 |
40.8 |
39.1 |
56 |
NA
|
39 |
43.9 |
41.9 |
39.1 |
62.9 |
54.1 |
43.9 |
39 |
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽ADS1 |
|
|
V
|
V
|
V
|
V
|
NA
|
NA
|
V
|
NA
|
V
|
V
|
NA
|
NA
|
V
|
V
|
V
|
V
|
NA
|
NA
|
V
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽ADS2 |
|
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
V
|
NA
|
NA
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
V
|
NA
|
V
|
|
|
|
|
|
|
|
|
|
|
|
|
再生桶槽ADS1 |
|
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
再生桶槽ADS2 |
|
|
NA
|
V
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
V
|
NA
|
NA
|
NA
|
V
|
V
|
NA
|
NA
|
NA
|
V
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水入口溫度(管路) |
|
℃ |
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出口溫度(管路) |
|
℃ |
14 |
13 |
25 |
14 |
NA
|
18 |
14 |
18 |
24 |
17 |
10 |
NA
|
15 |
25 |
27 |
17 |
13 |
24 |
25 |
15 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水入口壓力(管路) |
|
kg/cm2 |
6.7 |
6.1 |
6.1 |
6.3 |
NA
|
6.4 |
6 |
6 |
6.3 |
6.3 |
6.2 |
NA
|
6.2 |
6.2 |
6.4 |
6.3 |
6.1 |
6.3 |
6 |
6.2 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出口壓力(管路) |
|
kg/cm2 |
4.7 |
4.9 |
4.9 |
4.6 |
NA
|
5 |
5 |
4.6 |
4.7 |
4.8 |
4.9 |
NA
|
4.6 |
4.8 |
4.8 |
4.8 |
4.9 |
4.8 |
4.8 |
4.8 |
|
|
|
|
|
|
|
|
|
|
|
|
前置過濾器壓差 |
≦0.4 |
Bar |
0.1 |
0 |
0.1 |
0.1 |
NA
|
0.1 |
0.1 |
0.08 |
0.1 |
0.1 |
0.1 |
NA
|
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
|
|
|
|
|
|
|
|
|
|
|
|
後置過濾器壓差 |
≦0.4 |
Bar |
0 |
0 |
0.1 |
0.1 |
NA
|
0.1 |
0.01 |
0.01 |
0.1 |
0.1 |
0.1 |
NA
|
0.01 |
0.01 |
0.1 |
0.1 |
0.1 |
0.1 |
0.01 |
0.01 |
|
|
|
|
|
|
|
|
|
|
|
|
却水器檢查 |
|
|
V
|
V
|
V
|
V
|
NA
|
V
|
V
|
V
|
V
|
V
|
V
|
NA
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
|
|
|
|
|
|
|
|
|
|
|
| 備註 |
1.(V):正常/(X):異常;有操作參數則需填入檢查數據。
2.若該設備無此項檢查項目時,請填寫NA。
3.此表單由廠房設施部存查,保存期限三年。
|
| 紀錄者 |
洪耀懋
|
洪耀懋
|
王清雲
|
王清雲
|
王清雲
|
王清雲
|
張家韋
|
張家韋
|
王清雲
|
王清雲
|
王清雲
|
王清雲
|
張家韋
|
張家韋
|
王清雲
|
王清雲
|
王清雲
|
王清雲
|
張家韋
|
張家韋
|
|
|
|
|
|
|
|
|
|
|
|