| 檢查項目 | 參考值 | 單位 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 冰水進水壓力 | ≧1.5 | Kg/cm2 | 1.5 | 1.5 | 1.4 | 1.4 | 1.4 | 1.4 | 1.6 | 1.6 | 1.4 | 1.4 | 1.3 | 1.3 | 1.6 | 1.5 | NA | 1.4 | 1.4 | NA | NA | 1.6 | |||||||||||
| 冰水出水壓力 | ≧0.5 | Kg/cm2 | 1 | 1 | 1.3 | 1.3 | 1.3 | 1.3 | 1.2 | 1.2 | 1.3 | 1.3 | 1.2 | 1.2 | 1.2 | 0.8 | NA | 1.3 | 1.3 | NA | NA | 1.2 | |||||||||||
| 冰水進水溫度 | ℃ | 7 | 7 | 6 | 6 | 6 | 6 | 7 | 7 | 6 | 5 | 6 | 6 | 7 | 7 | NA | 6 | 6 | NA | NA | 7 | ||||||||||||
| 冰水出水溫度 | ℃ | 14 | 14 | 14 | 14 | 14 | 13 | 12 | 12 | 13 | 14 | 12 | 13 | 12 | 11 | NA | 13 | 13 | NA | NA | 12 | ||||||||||||
| 檢查皮帶或連軸器 | V | V | V | V | V | V | V | V | V | V | V | V | V | V | NA | V | V | NA | NA | V | |||||||||||||
| 檢查風車馬達軸承是否異聲 | V | V | V | V | V | V | V | V | V | V | V | V | V | V | NA | V | V | NA | NA | V | |||||||||||||
| 檢查冰水電動閥 | V | V | V | V | V | V | V | V | V | V | V | V | V | V | NA | V | V | NA | NA | V | |||||||||||||
| 檢查溫度控制器 | V | V | V | V | V | V | V | V | V | V | V | V | V | V | NA | V | V | NA | NA | V | |||||||||||||
| 檢查排水管路 | V | V | V | V | V | V | V | V | V | V | V | V | V | V | NA | V | V | NA | NA | V | |||||||||||||
| 檢查濾網 | V | V | V | V | V | V | V | V | V | V | V | V | V | V | NA | V | V | NA | NA | V | |||||||||||||
| 檢查加濕器 | V | V | V | V | V | V | V | V | V | V | V | V | V | V | NA | V | V | NA | NA | V | |||||||||||||
| 檢查加熱器 | V | V | V | V | V | V | V | V | V | V | V | V | V | V | NA | V | V | NA | NA | V | |||||||||||||
| 備註 | 1.(V):正常/(X):異常;有操作參數則需填入檢查數據。 2.若該設備無此項檢查項目時,請填寫NA。 3.此表單由廠房設施部存查,保存期限三年。 | ||||||||||||||||||||||||||||||||
| 紀錄者 | 黃立凱 | 黃立凱 | 黃志銘 | 黃志銘 | 黃志銘 | 黃志銘 | 康晉昇 | 康晉昇 | 黃志銘 | 黃志銘 | 黃志銘 | 黃志銘 | 康晉昇 | 康晉昇 | 黃志銘 | 黃志銘 | 康晉昇 | ||||||||||||||||