- 首頁
- 巡檢紀錄
- 設備巡檢結果
- 詳細資訊
- 表單顯示
勇日 DB-30LD 吸附式乾燥機AT-MDM-B2-04
設備巡檢紀錄 - 勇日 DB-30LD 吸附式乾燥機檢查表
|
檢查項目
|
參考值
|
單位
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
13
|
14
|
15
|
16
|
17
|
18
|
19
|
20
|
21
|
22
|
23
|
24
|
25
|
26
|
27
|
28
|
29
|
30
|
31
|
|
出口露點溫度 |
≦-40 |
℃ |
-80.6 |
-55.5 |
-71.3 |
-81.9 |
-84.1 |
-57.6 |
-57.6 |
-72.1 |
-79.3 |
-81.2 |
-78.5 |
-77 |
-53.2 |
-57.9 |
-40.8 |
-77.7 |
-78.7 |
-78.6 |
-76.8 |
-84.7 |
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽壓力 |
|
Bar |
6.92 |
6.93 |
6.93 |
6.92 |
6.93 |
6.94 |
6.89 |
6.89 |
6.95 |
6.84 |
6.98 |
6.92 |
6.84 |
6.89 |
6.83 |
6.80 |
6.61 |
6.86 |
6.81 |
6.89 |
|
|
|
|
|
|
|
|
|
|
|
|
再生加熱溫度TT1 |
15~200 |
℃ |
55.3 |
37.2 |
170.2 |
173.3 |
38.3 |
36.9 |
36.0 |
176.8 |
175.6 |
173.1 |
37.5 |
37.9 |
37.1 |
37.2 |
36.4 |
177.7 |
38.5 |
174.5 |
177.5 |
38.3 |
|
|
|
|
|
|
|
|
|
|
|
|
再生端出口溫度TT2 |
|
℃ |
56.4 |
37.7 |
36.5 |
104.9 |
38.9 |
38.8 |
36.8 |
36.2 |
39.6 |
52.9 |
39.6 |
38.3 |
38.4 |
37.7 |
37.5 |
38.9 |
39 |
40.5 |
39.1 |
38.9 |
|
|
|
|
|
|
|
|
|
|
|
|
再生冷卻端入口溫度TT3 |
|
℃ |
57.6 |
32.8 |
40.8 |
36.1 |
41.2 |
32.2 |
31.8 |
42.3 |
34.7 |
57.4 |
33 |
35.6 |
32.3 |
32.9 |
32.2 |
34.0 |
39.8 |
54 |
39.8 |
48.3 |
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽ADS1 |
|
|
V
|
NA
|
NA
|
V
|
NA
|
V
|
V
|
NA
|
V
|
NA
|
V
|
NA
|
V
|
NA
|
V
|
V
|
NA
|
NA
|
V
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽ADS2 |
|
|
NA
|
V
|
V
|
NA
|
V
|
NA
|
NA
|
V
|
NA
|
V
|
NA
|
V
|
NA
|
V
|
NA
|
NA
|
V
|
V
|
NA
|
V
|
|
|
|
|
|
|
|
|
|
|
|
|
再生桶槽ADS1 |
|
|
NA
|
NA
|
V
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
V
|
|
|
|
|
|
|
|
|
|
|
|
|
再生桶槽ADS2 |
|
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水入口溫度(管路) |
|
℃ |
11 |
17 |
22 |
24 |
12 |
18 |
19 |
21 |
24 |
24 |
15 |
15 |
18 |
16 |
20 |
23 |
15 |
22 |
16 |
8 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出口溫度(管路) |
|
℃ |
16 |
14 |
18 |
22 |
12 |
15 |
16 |
18 |
20 |
22 |
15 |
15 |
18 |
14 |
18 |
20 |
15 |
20 |
14 |
9 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水入口壓力(管路) |
|
kg/cm2 |
7.2 |
7.2 |
7 |
7 |
7 |
7 |
7 |
7.2 |
7 |
7.2 |
7 |
7 |
7 |
7 |
7.2 |
7 |
7 |
7 |
7 |
7.2 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出口壓力(管路) |
|
kg/cm2 |
7.8 |
7.6 |
7.6 |
7.5 |
7.8 |
7.6 |
7.6 |
7.7 |
7.6 |
7.6 |
7.8 |
7.8 |
7.8 |
7.6 |
7.6 |
7.6 |
7.8 |
7.8 |
7.6 |
7.6 |
|
|
|
|
|
|
|
|
|
|
|
|
前置過濾器壓差 |
≦0.4 |
Bar |
0.05 |
0.05 |
0.02 |
0.01 |
0.01 |
0.01 |
0.03 |
0.02 |
0.02 |
0.02 |
0.01 |
0.01 |
0.01 |
0.02 |
0.02 |
0.02 |
0.01 |
0.01 |
0.02 |
0.02 |
|
|
|
|
|
|
|
|
|
|
|
|
後置過濾器壓差 |
≦0.4 |
Bar |
0.05 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
|
|
|
|
|
|
|
|
|
|
|
|
却水器檢查 |
|
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
|
|
|
|
|
|
|
|
|
|
|
| 備註 |
1.(V):正常/(X):異常;有操作參數則需填入檢查數據。
2.若該設備無此項檢查項目時,請填寫NA。
3.此表單由廠房設施部存查,保存期限三年。
|
| 紀錄者 |
楊植鈞
|
楊植鈞
|
楊植鈞
|
張家韋
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
黃立凱
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
|
|
|
|
|
|
|
|
|
|
|