- 首頁
- 巡檢紀錄
- 設備巡檢結果
- 詳細資訊
- 表單顯示
勇日 DB-30LD 吸附式乾燥機AT-MDM-B2-03
設備巡檢紀錄 - 勇日 DB-30LD 吸附式乾燥機檢查表
|
檢查項目
|
參考值
|
單位
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
13
|
14
|
15
|
16
|
17
|
18
|
19
|
20
|
21
|
22
|
23
|
24
|
25
|
26
|
27
|
28
|
29
|
30
|
31
|
|
出口露點溫度 |
≦-40 |
℃ |
-47.4 |
-49.3 |
-48.6 |
-48.8 |
-48.8 |
-46.3 |
-49.6 |
-47.9 |
-47.9 |
-40.4 |
-47.7 |
-49.5 |
-48.4 |
-45 |
-49.2 |
-48.4 |
-43.3 |
-48.2 |
-49.1 |
-49.7 |
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽壓力 |
|
Bar |
7.01 |
7.02 |
7.00 |
7.02 |
7.01 |
7.01 |
6.95 |
7.01 |
7.05 |
6.93 |
7.03 |
6.94 |
6.9 |
6.97 |
6.90 |
6.95 |
6.83 |
6.93 |
6.91 |
7.00 |
|
|
|
|
|
|
|
|
|
|
|
|
再生加熱溫度TT1 |
15~200 |
℃ |
158.2 |
172.1 |
171.3 |
170.3 |
174.2 |
39.3 |
43.2 |
64.3 |
165.3 |
41.3 |
170.3 |
49.2 |
78.2 |
39.3 |
43.3 |
46.3 |
42.2 |
155.3 |
43.2 |
43.2 |
|
|
|
|
|
|
|
|
|
|
|
|
再生端出口溫度TT2 |
|
℃ |
42.4 |
43.0 |
39.1 |
37.2 |
38.1 |
37.2 |
41.1 |
64.1 |
39.1 |
37.2 |
35.2 |
50.2 |
79.1 |
37.2 |
41.1 |
46.1 |
40.1 |
27.1 |
42.1 |
42.1 |
|
|
|
|
|
|
|
|
|
|
|
|
再生冷卻端入口溫度TT3 |
|
℃ |
44.6 |
32.1 |
30.2 |
27.1 |
29.2 |
29.2 |
39.2 |
100.2 |
44.2 |
31.1 |
37.3 |
62.1 |
167.2 |
30.2 |
40.2 |
56.3 |
34.2 |
28.2 |
40.1 |
43.2 |
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽ADS1 |
|
|
NA
|
V
|
V
|
V
|
V
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
V
|
V
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
使用桶槽ADS2 |
|
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
V
|
V
|
V
|
V
|
NA
|
NA
|
NA
|
V
|
V
|
V
|
NA
|
V
|
V
|
|
|
|
|
|
|
|
|
|
|
|
|
再生桶槽ADS1 |
|
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
V
|
NA
|
V
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
V
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
再生桶槽ADS2 |
|
|
NA
|
V
|
V
|
V
|
V
|
V
|
NA
|
NA
|
NA
|
NA
|
NA
|
V
|
V
|
NA
|
NA
|
NA
|
NA
|
V
|
NA
|
NA
|
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水入口溫度(管路) |
|
℃ |
16 |
16 |
16 |
15 |
15 |
15 |
15 |
13 |
15 |
15 |
15 |
13 |
14 |
15 |
15 |
14 |
15 |
16 |
16 |
14 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出口溫度(管路) |
|
℃ |
18 |
19 |
19 |
20 |
19 |
15 |
18 |
15 |
18 |
17 |
17 |
15 |
16 |
16 |
17 |
15 |
17 |
20 |
19 |
16 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水入口壓力(管路) |
|
kg/cm2 |
7.2 |
7.7 |
7.7 |
7.8 |
7.6 |
7.8 |
7.7 |
7.3 |
7.6 |
7.7 |
7.8 |
7.2 |
7.6 |
7.6 |
7.7 |
7.4 |
7.6 |
7.6 |
7.4 |
7.6 |
|
|
|
|
|
|
|
|
|
|
|
|
冷卻水出口壓力(管路) |
|
kg/cm2 |
6.2 |
6.4 |
6.4 |
6.8 |
6.8 |
7.6 |
6.4 |
6.7 |
6.5 |
6.4 |
5.6 |
6.4 |
5.8 |
6.4 |
6.4 |
6.6 |
6 |
5.8 |
6.4 |
6.4 |
|
|
|
|
|
|
|
|
|
|
|
|
前置過濾器壓差 |
≦0.4 |
Bar |
0.1 |
0.01 |
0.01 |
0.01 |
0.05 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
|
|
|
|
|
|
|
|
|
|
|
|
後置過濾器壓差 |
≦0.4 |
Bar |
0.1 |
0.01 |
0.01 |
0.01 |
0.05 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
|
|
|
|
|
|
|
|
|
|
|
|
却水器檢查 |
|
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
V
|
|
|
|
|
|
|
|
|
|
|
|
| 備註 |
1.(V):正常/(X):異常;有操作參數則需填入檢查數據。
2.若該設備無此項檢查項目時,請填寫NA。
3.此表單由廠房設施部存查,保存期限三年。
|
| 紀錄者 |
楊植鈞
|
楊植鈞
|
楊植鈞
|
張家韋
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
黃立凱
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
|
|
|
|
|
|
|
|
|
|
|