- 首頁
- 巡檢紀錄
- 設備巡檢結果
- 詳細資訊
- 表單顯示
TRANE 500HP 離心式冰水主機AT-CHM-B2-03
設備巡檢紀錄 - TRANE 離心式冰水主機檢查表
|
檢查項目
|
參考值
|
單位
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
13
|
14
|
15
|
16
|
17
|
18
|
19
|
20
|
21
|
22
|
23
|
24
|
25
|
26
|
27
|
28
|
29
|
30
|
31
|
|
電流 L1 |
|
A |
325 |
332 |
328 |
317 |
313 |
308 |
320 |
317 |
312 |
315 |
313 |
328 |
320 |
317 |
320 |
327 |
327 |
330 |
328 |
297 |
|
|
|
|
|
|
|
|
|
|
|
|
電流 L2 |
|
A |
337 |
342 |
338 |
327 |
322 |
318 |
330 |
327 |
322 |
325 |
325 |
338 |
330 |
328 |
330 |
332 |
337 |
340 |
337 |
305 |
|
|
|
|
|
|
|
|
|
|
|
|
電流 L3 |
|
A |
323 |
328 |
325 |
312 |
310 |
307 |
317 |
312 |
308 |
313 |
310 |
325 |
317 |
315 |
317 |
323 |
322 |
327 |
325 |
293 |
|
|
|
|
|
|
|
|
|
|
|
|
實際電流值 |
|
% |
72.3 |
76.0 |
75.6 |
72.3 |
71.6 |
71.2 |
73.0 |
73.0 |
71.9 |
72.6 |
71.9 |
75.3 |
73.4 |
73.0 |
73.4 |
74.9 |
74.9 |
25.6 |
74.5 |
67.8 |
|
|
|
|
|
|
|
|
|
|
|
|
吐出油壓 |
40~103 |
Kpa |
77.1 |
78.9 |
78.5 |
77.7 |
76.2 |
76.4 |
75.2 |
77.7 |
77.5 |
78.4 |
77.9 |
80.2 |
76.3 |
78.2 |
78.2 |
76.8 |
76.1 |
75.7 |
76.2 |
76.1 |
|
|
|
|
|
|
|
|
|
|
|
|
油槽壓力 |
≧-83 |
Kpa |
-47.1 |
-46.7 |
-46.7 |
-48.4 |
-48 |
-48.9 |
-48.0 |
-47.9 |
-48.0 |
-46.7 |
-45.4 |
-45.5 |
-46.7 |
-47.6 |
-47.5 |
-47.6 |
-47.1 |
-45.3 |
-47.1 |
-48.9 |
|
|
|
|
|
|
|
|
|
|
|
|
油槽壓差 |
82~170 |
Kpa |
125.6 |
125.9 |
126.8 |
123.7 |
124.7 |
123.5 |
124.3 |
126.5 |
124.3 |
124.2 |
126.7 |
129.3 |
126.7 |
124.4 |
125.8 |
125.4 |
127.6 |
125.9 |
126.8 |
123.2 |
|
|
|
|
|
|
|
|
|
|
|
|
油槽溫度 |
40~66 |
℃ |
42.8 |
42.9 |
43.0 |
43.3 |
42.8 |
43.4 |
43.1 |
43.4 |
43.3 |
43.0 |
43.2 |
43.6 |
43.1 |
43.0 |
43.0 |
43.0 |
43.2 |
43.2 |
43.1 |
43.8 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器冷媒壓力 |
-80~-30 |
Kpa |
-55.4 |
-55.4 |
-55.4 |
-55.7 |
-55.5 |
-55.9 |
-55.9 |
-55.6 |
-55.5 |
-55.9 |
-55.4 |
-55.4 |
-55.5 |
-55.8 |
-55.4 |
-55.5 |
-55.5 |
-55.5 |
-55.4 |
-55.9 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器冷媒壓力 |
0~83 |
Kpa |
54.9 |
57.8 |
58.4 |
51.1 |
51 |
48 |
51.5 |
52.0 |
50.0 |
53.1 |
58.4 |
63.1 |
56.2 |
53.2 |
54.5 |
54.1 |
56.7 |
60.5 |
56.5 |
47.6 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器趨近溫度 |
|
℃ |
1.1 |
1.0 |
1.0 |
1.1 |
1 |
1.2 |
1.1 |
1.1 |
1.1 |
1.0 |
0.9 |
1 |
1.1 |
1.1 |
1.1 |
1.1 |
1 |
1 |
1.1 |
1.1 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器趨近溫度 |
|
℃ |
3.1 |
3.0 |
2.9 |
2.8 |
2.8 |
2.9 |
2.9 |
2.8 |
2.7 |
2.8 |
2.7 |
2.8 |
2.8 |
2.8 |
2.7 |
2.9 |
2.8 |
2.8 |
2.8 |
2.6 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器進水溫度 |
|
℃ |
11.8 |
11.9 |
11.9 |
11.7 |
11.6 |
11.6 |
11.7 |
11.8 |
11.6 |
11.6 |
11.6 |
11.8 |
11.8 |
11.7 |
11.7 |
11.8 |
11.8 |
11.9 |
11.8 |
11.5 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器出水溫度 |
6~12 |
℃ |
7.2 |
7.2 |
7.2 |
7.1 |
7.1 |
7.1 |
7.2 |
7.1 |
7.1 |
7.1 |
7.1 |
7.2 |
7.2 |
7.2 |
7.2 |
7.2 |
7.1 |
7.1 |
7.1 |
7.1 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器進水溫度 |
≦32 |
℃ |
31.1 |
31.6 |
31.8 |
30.7 |
30.7 |
30.1 |
30.4 |
30.5 |
30.3 |
30.5 |
31.7 |
32 |
31.1 |
30.5 |
30.8 |
30.5 |
30.9 |
31.5 |
30.5 |
29.8 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器出水溫度 |
≦37 |
℃ |
36.0 |
36.7 |
37.0 |
35.6 |
35.6 |
35.1 |
35.5 |
35.7 |
35.4 |
35.7 |
36.8 |
37 |
36.5 |
36.0 |
36.3 |
36.1 |
36.6 |
37 |
36.3 |
35.0 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器進出水壓差 |
≧0.3 |
kg/cm2 |
0.5 |
0.6 |
0.6 |
0.4 |
0.3 |
0.3 |
0.6 |
0.6 |
0.7 |
0.7 |
0.3 |
0.3 |
0.3 |
0.6 |
0.6 |
0.6 |
0.3 |
0.3 |
0.3 |
0.6 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器進出水壓差 |
≧0.5 |
kg/cm2 |
1.1 |
1.0 |
1.0 |
1.2 |
0.5 |
0.5 |
1.0 |
1.0 |
1.0 |
1.0 |
0.5 |
0.5 |
0.5 |
1.0 |
1.7 |
2 |
0.5 |
0.5 |
1.0 |
2.0 |
|
|
|
|
|
|
|
|
|
|
|
| 備註 |
1.(V):正常/(X):異常;有操作參數則需填入檢查數據。
2.若該設備無此項檢查項目時,請填寫NA。
3.此表單由廠房設施部存查,保存期限三年。
|
| 紀錄者 |
楊植鈞
|
楊植鈞
|
楊植鈞
|
張家韋
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
黃立凱
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
|
|
|
|
|
|
|
|
|
|
|