TRANE 500HP 離心式冰水主機AT-CHM-B2-04
設備巡檢紀錄 - TRANE 離心式冰水主機檢查表
|
檢查項目
|
參考值
|
單位
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
13
|
14
|
15
|
16
|
17
|
18
|
19
|
20
|
21
|
22
|
23
|
24
|
25
|
26
|
27
|
28
|
29
|
30
|
31
|
|
電流 L1 |
|
A |
333 |
336 |
331 |
311 |
316 |
310 |
319 |
323 |
313 |
319 |
319 |
335 |
325 |
316 |
323 |
323 |
325 |
335 |
326 |
291 |
|
|
|
|
|
|
|
|
|
|
|
|
電流 L2 |
|
A |
336 |
341 |
338 |
316 |
321 |
314 |
323 |
328 |
318 |
326 |
325 |
339 |
328 |
325 |
326 |
328 |
330 |
342 |
328 |
296 |
|
|
|
|
|
|
|
|
|
|
|
|
電流 L3 |
|
A |
328 |
331 |
328 |
308 |
313 |
304 |
314 |
319 |
310 |
316 |
316 |
33 |
319 |
314 |
319 |
319 |
321 |
333 |
320 |
288 |
|
|
|
|
|
|
|
|
|
|
|
|
實際電流值 |
|
% |
73.5 |
75.7 |
75.1 |
70.1 |
71.6 |
69.4 |
72.0 |
72.8 |
70.5 |
72.4 |
72 |
75.7 |
73.2 |
72.0 |
72.5 |
72.8 |
72.8 |
75.3 |
72.6 |
65.7 |
|
|
|
|
|
|
|
|
|
|
|
|
吐出油壓 |
40~103 |
Kpa |
92.9 |
92.9 |
93.3 |
93.2 |
93.7 |
93.7 |
93.0 |
94.5 |
94.4 |
94.4 |
95.9 |
94.5 |
94 |
95.2 |
94.3 |
92.8 |
93 |
92 |
92.7 |
92.0 |
|
|
|
|
|
|
|
|
|
|
|
|
油槽壓力 |
≧-83 |
Kpa |
-51.0 |
-50.6 |
-50.6 |
-52.4 |
-52.3 |
-52.4 |
-52.3 |
-51.5 |
-51.9 |
-50.6 |
-43.3 |
-49.3 |
-50.6 |
-51.9 |
-51.9 |
-51.9 |
-51 |
-50.6 |
-51.5 |
-52.7 |
|
|
|
|
|
|
|
|
|
|
|
|
油槽壓差 |
82~170 |
Kpa |
144.6 |
144.4 |
144.3 |
146.3 |
146.1 |
146.3 |
145.0 |
145.2 |
145.4 |
145.0 |
144.7 |
144 |
145 |
146.2 |
145.5 |
144.0 |
144.6 |
144.2 |
144.5 |
145.5 |
|
|
|
|
|
|
|
|
|
|
|
|
油槽溫度 |
40~66 |
℃ |
48.9 |
48.9 |
49.0 |
48.4 |
48.9 |
48 |
48.9 |
48.9 |
48.8 |
48.9 |
48.9 |
49.1 |
48.9 |
48.9 |
49.0 |
48.9 |
43 |
48.9 |
48.9 |
48.8 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器冷媒壓力 |
-80~-30 |
Kpa |
-55.4 |
-55.5 |
-55.4 |
-55.4 |
-55.5 |
-55.5 |
-55.5 |
-55.4 |
-55.5 |
-55.5 |
-55.4 |
-55.4 |
-55.4 |
-55.4 |
-55.9 |
-55.5 |
-55.4 |
-55.9 |
-55.5 |
-55.4 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器冷媒壓力 |
0~83 |
Kpa |
41.1 |
44.1 |
44.6 |
36 |
37.8 |
34.6 |
36.3 |
38.1 |
35.5 |
38.5 |
44.1 |
49 |
41.1 |
37.7 |
39.0 |
37.7 |
33.8 |
43.3 |
40.0 |
31.2 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器趨近溫度 |
|
℃ |
0.8 |
0.8 |
0.8 |
0.8 |
0.9 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.9 |
0.9 |
0.8 |
0.8 |
0.8 |
0.8 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器趨近溫度 |
|
℃ |
2.3 |
2.3 |
2.2 |
2 |
2.1 |
2 |
2.0 |
2.1 |
2.0 |
2.1 |
2 |
2.2 |
2.1 |
2.1 |
2.1 |
2.1 |
2.2 |
2.2 |
2.1 |
1.8 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器進水溫度 |
|
℃ |
12.1 |
12.1 |
12.1 |
11.9 |
11.9 |
11.2 |
11.9 |
12.0 |
11.9 |
11.9 |
12 |
12.2 |
12 |
11.9 |
11.9 |
12.0 |
12 |
12.1 |
12.0 |
11.7 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器出水溫度 |
6~12 |
℃ |
7.1 |
6.9 |
7.0 |
7.1 |
6.9 |
6.9 |
6.9 |
6.9 |
7.0 |
6.9 |
6 |
7 |
7 |
6.9 |
6.9 |
7.0 |
6 |
6 |
6 |
7.0 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器進水溫度 |
≦32 |
℃ |
31.0 |
31.6 |
31.8 |
30.6 |
30.7 |
30.1 |
30.3 |
30.5 |
30.2 |
30.5 |
31.6 |
32 |
31.1 |
30.5 |
30.9 |
30.5 |
30.9 |
31.4 |
30.5 |
29.8 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器出水溫度 |
≦37 |
℃ |
34.9 |
35.5 |
35.7 |
34.1 |
34.4 |
33.2 |
34.1 |
34.4 |
33.9 |
34.2 |
35.4 |
35 |
34.9 |
34.2 |
34.6 |
34.3 |
34.9 |
35.4 |
34.6 |
33.1 |
|
|
|
|
|
|
|
|
|
|
|
|
蒸發器進出水壓差 |
≧0.3 |
kg/cm2 |
0.6 |
1.1 |
1.1 |
1 |
0.6 |
0.3 |
1.2 |
1.2 |
1.2 |
1.2 |
0.3 |
0.3 |
0.3 |
1.2 |
1.2 |
1.1 |
0.3 |
0.3 |
1.1 |
1.1 |
|
|
|
|
|
|
|
|
|
|
|
|
冷凝器進出水壓差 |
≧0.5 |
kg/cm2 |
1.5 |
0.7 |
0.5 |
0.8 |
1 |
0.5 |
1.6 |
1.2 |
1.1 |
0.8 |
0.5 |
0.5 |
0.5 |
1.3 |
0.9 |
1.4 |
0.5 |
0.5 |
1.2 |
2.2 |
|
|
|
|
|
|
|
|
|
|
|
| 備註 |
1.(V):正常/(X):異常;有操作參數則需填入檢查數據。
2.若該設備無此項檢查項目時,請填寫NA。
3.此表單由廠房設施部存查,保存期限三年。
|
| 紀錄者 |
楊植鈞
|
楊植鈞
|
楊植鈞
|
張家韋
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
黃立凱
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
楊植鈞
|
黃立凱
|
黃立凱
|
楊植鈞
|
楊植鈞
|
|
|
|
|
|
|
|
|
|
|
|